How do I create a motor start/stop seal-in circuit in FX5U ladder?
Place the healthy stop and overload conditions in series, then place the start contact in parallel with the output holding contact before the motor output coil.
Practical explanation
This gives stop priority when the stop/healthy condition opens.
The PLC logic does not replace hardwired safety and overload protection.
Check in this order
- 1Confirm whether stop and overload inputs are wired normally closed.
- 2Add all machine permissives.
- 3Test loss and restoration of PLC power.
Ladder instruction example
LD X1 AND X2 MPS AND X0 MPP OR Y0 OUT Y0
Example only—allocate devices and interlocks for your own project.
Devices and registers
X0: start pushbutton
X1: stop circuit healthy
X2: overload healthy
Y0: motor contactor command
Safety: Use certified hardwired safety circuits and a correctly rated motor protection device.