COMMUNICATION • FX5U / GX WORKS3

Why is my FX5U RS-485 device not communicating?

Check the selected serial channel, polarity, common/reference connection, station number and the complete serial format before changing the PLC program.

Practical explanation

A and B terminal naming is not consistent across every manufacturer, so confirm both manuals rather than relying on the letters alone.

Communication settings are configured for the actual FX5 port/module in GX Works3.

Check in this order

  1. 1Confirm CH1/CH2/CH3/CH4 hardware assignment.
  2. 2Compare baud, data bits, parity and stop bits.
  3. 3Verify slave address and protocol.
  4. 4Check termination and cable topology.

Related verified answers

Still need help with your machine?

Ask a real question in the community and include the PLC model, software version, error and what you already checked.